Application errors and disadvantages of frequency converter and Countermeasures

2023-05-20 13:00:28

Error 1: connect electromagnetic switch and electromagnetic contactor in inverter output circuit


In practical application, some occasions need to use the contactor to switch the frequency converter: for example, when the frequency conversion fault is switched to the power frequency state, or when one motor fails, the frequency converter turns to drive another motor and so on. Therefore, many users will think that it is a standard configuration to install electromagnetic switch and electromagnetic contactor in the inverter output circuit, which is a safe way to disconnect the power supply. In fact, there are great hidden dangers in this practice.


Disadvantages: when the frequency converter is still in operation, the contactor is first disconnected, and the load is suddenly interrupted. The surge current will make the over-current protection act, which will have a certain impact on the rectifier inverter main circuit. Serious, even make inverter output module IGBT damage. At the same time, when the inductive motor is loaded, the inductive magnetic field energy can not be released quickly, which will produce high voltage and damage the insulation of motor and connecting cable.


Coping strategy: connect the inverter output side with the motor cable directly. The normal start and stop of the motor can be realized by triggering the inverter control terminal, so as to achieve the effect of soft start and soft stop. If the contactor must be used at the output side of the frequency converter, the necessary control interlock must be carried out between the output of the frequency converter and the action of the contactor, so as to ensure that the contactor can act only when there is no output of the frequency converter.


Application errors and disadvantages of frequency converter and Countermeasures


Error 2: when the equipment is out of service, disconnect the AC input power of the inverter


In the normal shutdown of the equipment, many users are used to disconnect the AC input power switch of the inverter, thinking that it is safer and can save energy.


Disadvantages: this approach, on the surface, seems to be able to protect the inverter from the impact of power failure. In fact, the inverter is not charged for a long time, plus the influence of the environmental humidity on the site, which will cause the internal circuit board to be damped and slowly oxidize and gradually appear short circuit phenomenon. This is the reason why soft faults are frequently reported when the inverter is powered off for a period of time.


Coping strategy: in addition to equipment maintenance, the frequency converter should be kept in a state of electrification for a long time. In addition, the upper and lower fans of the frequency conversion control cabinet should be turned on, desiccant should be placed in the cabinet or automatic temperature and humidity control heater should be installed to maintain ventilation and dry environment.


Error 3: frequency converter control cabinet installed in open air or dust environment adopts sealed type


In some factories, mines, basements, outdoor installation and use of inverter control cabinet, will withstand such as high temperature, dust, humidity and other harsh environment. For this reason, many users will choose sealed type frequency conversion cabinet. Although to a certain extent, this can play a rain proof, dust-proof effect, but also brings the problem of poor heat dissipation of the inverter.


Disadvantages: the tight sealing of the control cabinet will cause overheating of internal components due to insufficient ventilation and heat dissipation capacity of frequency converter, and the protection action of thermal sensitive element will cause fault trip and forced shutdown of equipment.


Coping strategy: the upper part of the inverter control cabinet is equipped with a breathable rain cover with dust-proof filter screen as the exhaust port. The lower part is also slotted to install the fan with filter screen as the air inlet. It can form air circulation and filter dust in the environment at the same time. Cooling flow from the top to the bottom. The transverse installation distance between frequency converters shall not be less than 5mm, and the temperature of cooling air entering the frequency converter shall not exceed + 40 ℃. If the ambient temperature is above + 40 ℃ for a long time, the inverter should be installed in a small room with air conditioning.


In the control box, the frequency converter should be installed in the upper part of the box. It is absolutely not allowed to install the heating element or easily heating element close to the bottom of the converter.


Error 4: in order to improve the voltage quality, parallel power factor compensation capacitors are connected at the output end of frequency converter


Due to the limitation of power consumption capacity, the voltage quality of some enterprises can not be guaranteed, especially when the large-scale electrical equipment is put into operation, the bus voltage in the station will be reduced, and the load power factor will obviously decrease. In order to improve the voltage quality, the user usually parallels the power factor compensation capacitor at the inverter output end, hoping to improve the motor power factor.


Disadvantages: the power factor compensation capacitor and surge absorber are connected to the motor cable (between the frequency converter and the motor). Their influence will not only reduce the control accuracy of the motor, but also form transient voltage at the output side of the frequency converter, causing permanent damage to the frequency converter. If the power factor compensation capacitor is paralleled on the three-phase input line of the frequency converter, it must be ensured that the capacitor and the frequency converter will not be charged at the same time, so as to avoid damaging the inverter by surge voltage. The current of the frequency converter flows into the capacitor used to improve the power factor. Because of its charging current, the converter can not be started because of its over-current fault.


Coping strategy: remove the capacitor and operate. As for improving power factor, it is effective to connect AC reactor at the input side of frequency converter.


Mistake 5: circuit breaker is better than fuse for thermal overload and short circuit protection of frequency converter


Circuit breaker with perfect protection function has been widely used in power distribution equipment, which will replace the traditional fuse. Now many manufacturers produce complete sets of frequency control equipment, basically equipped with circuit breakers (air switches), in fact, there are some security risks.


Disadvantages: when the power cable is short circuited, the breaker protection action trip occurs due to the inherent action time of the circuit breaker. The official account is the pump housekeeper. During this period, the short circuit current will be introduced into the inverter, resulting in damage to the components.


Coping strategy: as long as the cable is selected according to the rated current, the inverter drive unit can protect itself, the input end and the motor cable to prevent thermal overload without additional thermal overload protection equipment. The configuration of fuse will protect the input cable in case of short circuit, reduce device damage and prevent damage to connected equipment in case of internal short circuit of transmission device.


Check that the action time of the configured fuse should be less than 0.5 s. The action time depends on the type of fuse (GG or AR), the impedance of the supply network, the cross-sectional area of the power cable, material and length. When the use of GG fuse exceeds 0.5 second action time, fast fuse (AR) can reduce the action time to an acceptable level in most cases. Fuses must be of the non delay type.


Circuit breakers do not provide fast enough protection for transmission equipment because they react more slowly than fuses. Therefore, fuses should be used instead of circuit breakers when quick protection is needed.


Error 6: only the load power should be considered in the selection of frequency converter


When purchasing frequency converters, many users usually match the capacity of frequency converters only according to the power of driving motor. In fact, the load driven by the motor is not the same, and the requirements for frequency converter are also different.


Disadvantages: due to the different load characteristics of the motor, if the comprehensive factors are not fully considered, the frequency converter may be damaged due to improper use. At the same time, the safety risk may be caused due to the lack of necessary brake unit and filter.


Coping strategy: according to the characteristics and types of load, the capacity and configuration of frequency converter should be selected reasonably.


1) Fans and pumps are the most common loads: the requirements for frequency converter are the simplest, as long as the capacity of frequency converter is equal to the capacity of motor (the capacity of air compressor, deep water pump, sediment pump and rapidly changing music fountain needs to be increased).


2) Crane load: the characteristic of this kind of load is that the impact is very big when starting, so the inverter is required to have a certain margin. At the same time, there will be energy feedback when the weight is lowered, so the brake unit or the common bus should be used.


3) Uneven load: some loads are sometimes light and sometimes heavy. At this time, the capacity of frequency converter should be selected according to the situation of heavy load, such as rolling mill machinery, crushing machinery, mixer, etc.


4) Large inertia load: such as centrifuge, punch press, rotary kiln of cement plant, such load inertia is very large, so it may oscillate when starting, and there is energy feedback when motor decelerates.. The frequency converter with larger capacity should be used to speed up the starting and avoid oscillation. Cooperate with brake unit to eliminate feedback electric energy.


Special frequency converter


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標題-8.png 0755-81719517
未標題-10.png0755-81719530 未標題-11.pngamb@ambition.com.cn
未標題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
黄色网页网址在线免费| 中文字幕亚洲综合久久菠萝蜜| 手机在线免费av| www成人免费视频| 在线观看黄色| 婷婷久久综合九色综合绿巨人| 国产精品婷婷| 美国三级日本三级久久99| 国产区在线观看成人精品| 四虎精品成人免费网站| 日韩三区视频| 欧美国产精品一区二区| 日本福利片在线| 日韩欧美黄色| 99re热视频精品| 国产精品女同互慰在线看| 中文字幕欧美日本乱码一线二线| 亚洲精品日韩专区silk| 欧美在线你懂的| 在线播放国产区| 九色丨porny丨| 7777精品伊人久久久大香线蕉的| 欧美日韩一卡二卡| 电影一区二区三区久久免费观看| 亚洲亚洲一区二区三区| 亚洲妇女av| 色777狠狠狠综合伊人| 久久亚洲精选| 亚洲自拍电影| 老色鬼精品视频在线观看播放| 国产色一区二区| 美女黄视频在线播放 | 国产精品极品在线观看| 国产精品草草| 国产成人精品一区二| 2023国产精品| 欧美性猛交xxxx久久久| h网址在线观看| 在线观看爽视频| 成人国产网站| 欧美成人精品一级| 国产综合色产| 综合久久一区二区三区| 黄色影院在线播放| 国产福利在线播放麻豆| 日韩成人视屏| 美女视频黄a大片欧美| 亚洲欧美国产毛片在线| 欧美精品高清视频| 日本中文字幕在线2020| 国模私拍视频在线播放| 91成人入口| 亚洲成在人线免费观看| 亚洲欧美另类图片| 久久一级大片| 91视频com| 亚洲伦理电影| 91麻豆精品国产综合久久久 | 国产精品成人一区二区三区夜夜夜| 欧美午夜影院在线视频| 青草在线视频| 亚洲一本二本| 日韩欧美国产激情| 在线观看a视频| 黄色污污视频在线观看| 怕怕欧美视频免费大全| 久久久一区二区三区捆绑**| sqte在线播放| 国产午夜亚洲精品羞羞网站| 天天操天天碰| 秋霞影院一区| 一区二区不卡在线播放| 欧美sm极限捆绑bd| 国产女人在线观看| 久久久成人网| 成人黄网18免费观看的网站| 日韩欧美中字| 黄动漫在线看| 青青草97国产精品免费观看 | 亚洲成人一品| 成人听书哪个软件好| 一区二区三区中文字幕| 欧美一个色资源| 在线精品视频一区| 福利微拍一区二区| а_天堂中文在线| 久久日文中文字幕乱码| 亚洲一二三专区| 成人精品久久| 99国产精品一区| 永久免费在线观看| 国产一区二区三区黄视频| 国产福利在线| 欧美精品资源| 久久精品亚洲精品国产欧美 | 日韩精品欧美| 午夜在线观看视频网站| 国产日韩高清在线| 综合国产视频| 亚洲一区二区四区蜜桃| 色婷婷精品视频| 亚洲自拍与偷拍| 无人区乱码一区二区三区| 午夜精品影院在线观看| 免费看久久久| 精品国产乱码久久久久久免费| 999精品嫩草久久久久久99| 国产91丝袜在线播放0| 男女网站在线观看| 中文字幕在线播放不卡一区| 韩国女主播一区二区三区| 欧美性videos高清精品| 日韩激情精品| 欧美日产在线观看| 亚洲精品乱码久久久久久蜜桃麻豆| 波波电影院一区二区三区| 在线免费av电影| 一区二区久久久久| 亚洲最大在线| 神马午夜伦理不卡| 91精品国产欧美日韩| 老牛影视一区二区三区| 在线三级中文| 久久久久国产精品麻豆ai换脸 | 亚洲福利久久| 国产高清一级毛片在线不卡| 2023国产精品| 欧美色就是色| 日本高清无吗v一区| 国产精品男女| 日韩精品一区二区三区中文不卡| 国产亚洲欧美日韩俺去了| 亚洲天天综合| 国产在线1区| 欧美激情一区二区在线| 911亚洲精品| 成年在线观看免费人视频| 91视视频在线观看入口直接观看www | 99在线免费观看| 国产精品18久久久| 青青草成人影院| 伊人发布在线| 欧美午夜精品一区| 精油按摩中文字幕久久| 色愁久久久久久| 在线中文视频| 99久久夜色精品国产网站| 成人黄色免费网站| 二区中文字幕| 欧美一区二区三区视频免费播放| 中文字幕在线视频一区| 91影院成人| 色呦呦在线资源| 欧美一级理论性理论a| 国产日韩亚洲欧美综合| 欧美色图激情小说| 日韩一区二区三区在线观看| 一区在线观看免费| 美女视频黄 久久| 久久久久久久久久久9不雅视频| 国产国产一区| 羞羞视频在线观看不卡| 在线免费观看av网站| 亚洲图片你懂的| 精品夜夜嗨av一区二区三区| 大黄网站在线观看| 成人av影视| 91精品婷婷国产综合久久性色| 亚洲欧洲中文日韩久久av乱码| 一本久久知道综合久久| 伊人网在线播放| 黄页在线观看视频| 欧美日韩一区在线| 91成人看片片| 欧美精品久久99久久在免费线 | 欧美日韩视频在线观看一区二区三区| 风间由美性色一区二区三区| 激情综合色播激情啊| 久久性天堂网| 国产精品一二| 日本欧美在线看| 99re视频这里只有精品| 亚洲视频免费在线观看| 欧洲激情一区二区| 美女激情网站| 超碰在线免费| 九色在线免费| 欧美日韩国产中文字幕在线| 九色在线视频蝌蚪| 最新中文字幕在线观看| 欧美唯美清纯偷拍| 一区二区在线观看av| 国产精品久久久久久久蜜臀| 精品96久久久久久中文字幕无| 日韩三区视频| 经典一区二区| 亚洲婷婷免费| 国产欧美午夜| 韩国在线视频一区| 成人av在线一区二区|